Disconnectors and Switchers

-

Horizontal CSH type

:

COELME EGIC

Back to home page Back to home page
 
Our products
Member of Southern States
 
 Disconnectors
 Power Switches
 

Horizontal CSH type


 The CSH, CSH-B are designed to provide a very compact and reliable solution with fault interrupting capability, particularly for transformer bays. They can replace a quick-whip disconnector to reach a fault clearing / fault making capability. CSH is a horizontal switcher, that can be coupled with a vertical break disconnector (CSH-B) for a visible gap opening. In this case, both equipments are operated by a single mechanism, ensuring an error-free switching sequence. The CSH series has the remarkable feature to adapt to a variety of phase-spacing, and reduce the height of the bay. Therefore, it is ideal for mobile power substation.

Both types are built around single gap SF6 puffer interrupters, which reliability has been proven over years.

RATED VALUES CSH
Rated voltage Ur (kV)
36
52
72,5
123
145
170
245
Rated lightning impulse
withstand voltage
TEUp (kV)
200
250
325 (IEC)
350 (ANSI)
550
650
750
900
TE : To Earth
AID : Across the Isolating Distance
Rated permanent current  Ir (A)
1250 A to 2000 A
Primary fault current interrupting   
20 kA ( 5 cycles)

20kA (6 cycles)

Number of full fault operations   
20
Fault closing rating   
5 time 40 kA


 

       