Disconnectors and Switchers

-

Double Break

:

COELME EGIC

Back to home page Back to home page
 
Our products
Member of Southern States
 
Disconnectors
 Centre Break
Double Break
 Vertical Break
 Knee-Type
 1-arm Pantograph
 2-arm Pantograph
 Earthing Switches
 Operating Mechanisms
Power Switchers
 Line Switcher
 CapSwitcher
 Circuit Switchers



 

Disconnectors : Double Break

Direct entry TCB Type

bullet_menu.gif The TCB, our direct entry design, is available up from 72.5 kV to 300 kV (BIL 1050) and either with gang or single pole operation. The moving arm enters directly the fixed contact, and few parts are in motion, making it an extremely reliable disconnecting solution.

Like for all our products, only premium quality materials are used to build this switch : the live parts are made of aluminium, hard drawn silver plated copper, with stainless steel hardware. The base frame and all steelworks are hot dip galvanised.

Options

  • Making and breaking of bus transfer currents up to 1600 A as per IEC 62271-102
  • 10 or 20 mm of ice operation ability (according to IEC 62271-102)
  • Custom HV terminals

RATED VALUES
Rated voltage Ur (kV)
72.5
123
145
170
245
300
Rated power frequency
withstand voltage
TEUd (kV)
140
230
275
325
395
460
380
AIDUd (kV)
160
265
315
375
460
530
435
Rated lightning impulse
withstand voltage
  
325 (IEC)
   
950 (IEC)
  
TEUp (kV)
350 (ANSI)
550
650
750
900 (ANSI)
1050
1050
 
1050
AIDUp (kV)
375
630
750
860
1050
1200
(+170)
Rated switching impulse
withstand voltage
TEUs (kV)
-
-
-
-
-
-
850
 
700
AIDUs (kV)
-
-
-
-
-
-
(+245)
TE : To Earth
AID : Across the Isolating Distance
Rated permanent current Ir (A)
Up to 4000 A IEC / ANSI
Rated short-time
withstand current
 Ik (kA)
Up to 63 kA / 3s
Rated peak withstand current Ip (kA)
Up to 160 kA
DIMENSIONS (mm)
A 
1280
1780
2200
2200
2880
3200
3200
 BIEC
770
1220
1500
1700
2100
2300
2300
ANSI
762
1143
1372
1575
2032
2337
2337
CIEC
970
1420
1720
1920
2370
2570
2570
ANSI
962
1343
1592
1795
2302
2607
2607
D 
900
1400
1800
1800
2300
2800
2800
E 
170
170
270
270
270
270
270
F 
-
-
-
-
270
270
270
G 
4Ø18
4Ø18
4Ø18
4Ø18
4Ø18
8Ø18
8Ø18




 



Disconnectors : Double Break : Direct entry TCB Type

 
     

Twist Motion STC Type

 The STC, with a twist motion design is available from 72.5 kV and up to 550 kV (BIL 1800), and is particularly suitable to EHV use, since the operation torque is independent from the arm length. After the arm has entered the fixed contact, the blades rotates on itself till it locks in the jaws, ensuring a smooth motion, and an exceptional short-circuit withstand ability.

Like for all our products, only premium quality materials are used to build this switch : the live parts are made of aluminium, hard drawn silver plated copper, with stainless steel hardware. The base frame and all steelworks are hot dip galvanised.

RATED VALUES
Rated voltage- Ur (kV)
72.5
123
145
170
245
300
362
420
550
Rated power frequency
withstand voltage
TEUd (kV)
140
230
275
325
395
460
380
450
520
620
AIDUd (kV)
160
265
315
375
460
530
435
520
610
800
Rated lightning impulse
withstand voltage
  
325 (IEC)
   
950 (IEC)
     
TEUp (kV)
350 (ANSI)
550
650
750
900 (ANSI)
1050
1050
1175
1425
1550
 
1050
1175
1425
1550
AIDUp (kV)
375
630
750
860
1050
1200
(+170)
(+205)
(+240)
(+315)
Rated switching impulse
withstand voltage
TEUs (kV)
-
-
-
-
-
-
850
950
1025
1175
 
700
800
900
900
AIDUs (kV)
-
-
-
-
-
-
(+245)
(+295)
(+345)
(+450)
TE : To Earth
AID : Across the Isolating Distance
Rated permanent current_ Ir (A)
Up to 4000 A IEC / ANSI
Rated short-time
withstand current
_ Ik (kA)
Up to 75 kA / 3s
Rated peak withstand current_ Ip (kA)
Up to 190 kA
DIMENSIONS (mm)
A_
1280
1780
2200
2200
2880
3500
3500
4200
4900
5500
 BIEC
770
1220
1500
1700
2100
2300
2300
2900
3350
3650
ANSI
762
1143
1372
1575
2032
2337
2337
-
3099
3861
CIEC
950
1400
1720
1920
2320
2520
2520
3280
3730
4030
ANSI
942
1323
1592
1795
2252
2557
2557
-
3479
4241
D_
1240
1640
2140
2140
2840
3070
3070
3640
4340
4840
E_
170
170
170
170
270
270
270
340
340
340
F_
-
-
-
-
-
270
270
340
340
340
G_
4Ø18
4Ø18
4Ø18
4Ø18
4Ø18
8Ø18
8Ø18
8Ø22
8Ø22
8Ø22


 

Disconnectors : Double Break : Twist Motion STC Type